www.lsis.biz
Super Solution
UL Molded case circuit breakers

Super Solution
Susol UL UTE and UTS series
UL UTE and
UTS series

Contents
>>>
Description
General Information
UTE100
UTS150
UTS250
UTS400
UTS600
UTS800
UTS1200
4
6
12
15
18
21
24
27
30

Susol circuit breakers are designed to protect electrical system from damage
caused by overload and short circuits.
UL MCCB
Series
For power distribution
▶
High breaking capacity
▶
Optimum coordination technique
▶
Powerful engineering tools
▶
Reverse feeding
The new Susol series with thermal-magnetic or electronic
circuit breakers are designed to protect electrical system
from damage caused by overload and short circuit.
NEW

To UTE100 from UTS600 frame circuit breakers are available with thermal-
magnetic and UTS800, UTS1200 are electronic trip units.
For motor protection & its control device
▶
Optimal overload protection
▶
Guaranteed Short Circuit Current Ratings
For controlling and disconnecting circuits
For extensive applications
▶
Wide range of optimized auxiliaries and accessories

MCCB Characteristics
6
Molded Case Circuit Breaker
�
Simplified product range
AF: 100AF, 150AF, 250AF, 400AF, 600AF, 800AF, 1200AF
Ampere Range: 15A ~ 1200A
Pole: 2P, 3P
�
High performance
Ultimate breaking capacity (kA rms)
Max 100kA @ 480VAC and 50kA @600V
�
Standards
World class with UL489
�
Various accessories
Electrical auxiliaries[AX, AL, UVT, SHT]
Extended and directed rotary handle
Flange handle with flexible cable and linkage
Variable depth mechanism
Locking devices
LUG for CU/AL cable with UL486
�
Various trip units
ATU: Adjustable thermal & magnetic unit
FMU: Adjustable thermal, fixed magnetic unit
FTU: Fixed thermal & magnetic unit
OCR: Electronic trip unit
MCP Characteristics
Motor Circuit Protector
�
Simplified product range
AF: 150AF, 250AF, 400AF, 600AF, 800AF, 1200AF
Ampere Range: 1.6A ~ 1200A
Only 3 Pole use
�
Standards
Instantaneous circuit breaker with UL489
Motor protector with MC and Relay with UL508
MCS Characteristics
Molded Case Switch
�
Simplified product range
AF: 100AF, 150AF, 250AF, 400AF, 600AF, 800AF, 1200AF
Ampere Range: 100A ~ 1200A
Pole: 2P, 3P
�
Standards
World class with UL489.

Technical Information
7
Handle position
�
Susol circuit breaker handle can assume any of the three positions: ON, TRIPPED, or OFF, as
shown on the right. The center tripped position provides positive visual indication that the circuit
breaker has tripped.
�
The circuit breaker can be reset by first pushing the handle to
“
OFF
”
position. Power can then
be restored to the load by pushing the handle to
“
ON
”
position.
�
The circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit
breaker. This should be used as part of a regular preventive maintenance program.
Operating mechanism
�
Susol circuit breakers have toggle handle operating mechanism, which also serves as switching
position indicator. The indicator shows the positions of: ON, OFF, and TRIPPED.
�
The circuit breakers have over- center toggle mechanism providing quick-make, quick-break
operation. The operating mechanism is also trip-free, which allows tripping even when the circuit
breaker handle is in
“
ON
”
position.
Optimized contactors with toggle mechanism
�
Easily induce ark mobility to grid direction
�
Rapidly redeploy the arc from moving contactor
�
Prevent contact tip from erosion
�
Reduce the amount of peak current during a short
circuit fault. It reduces the let through currents.
Open speed & contact force
�
Unvarying contact force regardless of Over-travel
�
Rapid open speed of moving contact due to
optimized cam curve regardless of trip signal.
[ON position]
[OFF position]
[TRIP position]
Angle
F
orce
Optimized
cam curve
Unvarying
contact
ON
OFF
TRIP

Field Installable Accessories
8
Figure 1: Field install accessories
Molded Case Circuit Breaker
Motor Circuit Protector
Molded Case Switch
Direct Rotary Handle
Extended Handle
Flange Cable Handle
Inner Accessories
(AL, AX, UVT, SHT)
Locking Device(Handle)
Mechanical Interlock
Terminal Shield
Interphase Barriers
Mechanical Lugs
Busbar Connectors
Control wire Terminal
Variable-depth Mechanism
Aux. Handle
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�

Electrical Characteristics
9
Maximum
Rated Current
(Amperes)
E N E N N
H L
2
3
2, 3
50
65
50
65
-
-
-
50
65
50
65
65
100
150
25
35
25
35
35
65
100
-
-
-
-
18
35
50
14
18
14
18
-
-
-
15~100A 15~100A
40~150A
-
-
●
-
●
●
●
●
●
- -
1.6~60A
100, 150A
- -
●
100A 100A
150A
●
●
●
●
●
●
●
●
●
●
●
●
-
-
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
-
●
●
-
●
●
-
●
●
●
●
●
●
●
●
-
●
●
●
●
●
W H
D
W H D
2.01(51)
5.12(130)
3.44(87.5)
4.13(105)
6.46(165) 3.44(87.5)
2.99(76)
5.12(130)
3.44(87.5)
4.13(105)
6.46(165) 3.44(87.5)
UTE100
UTE100
UTS150
Circuit Breaker
Breaker Type
Number of Poles
Breaker Capacity
120/240V
(kA rms)
240V
ac50~60Hz
480V
NEMA, UL
600V
600Y347V
MCCB(Trip Units)
Amperes
F: Fixed
A: Adjustable
ATU
T: Thermal
M: Magnetic
FMU
FTU
MCP
Amperes
MCP
MCS Amperes
MCS
Unit Mounted
Mechanical Lugs
Busbar connectors
Control Wire Terminal Kit
Interphase Barriers
Shunt Trip
Undervoltage Trip
Auxiliary Switch
Alarm Switch
Flange Cable Handle
Flange Variable-Depth Mechanism
Directly-Mounted Rotary Operating Handle
NEMA-Door-Mounted Operating Mechanisms
IEC-Door-Mounted Operating Mechanisms
Mechanical Interlocks
Handle Padlock Attachment
Dimensions
Inches(mm)
2-Pole
3-Pole

Electrical Characteristics
10
N H L N H L N H L
2, 3
2, 3
2, 3
65
100
150
65
100
150
65
100
150
35
65
100
35
65
100
35
65
100
18
35
50
18
35
50
18
35
50
150~250A
250~400A
500~600A
●
●
●
●
●
●
●
●
●
220A
320A
500A
●
●
●
175, 250A
400A
600A
●
●
●
●
●
●
●
●
●
●
●
●
●
-
-
-
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
W H D W H D W H D
4.13(105) 7.48(190) 3.44(87.5) 5.51(140) 11.42(290) 4.33(110) 5.51(140) 13.39(340) 4.33(110)
4.13(105) 7.48(190) 3.44(87.5) 5.51(140) 11.42(290) 4.33(110) 5.51(140) 13.39(340) 4.33(110)
UTS250
UTS400
UTS600
Maximum
Rated Current
(Amperes)
Circuit Breaker
Breaker Type
Number of Poles
Breaker Capacity
240V
(kA rms) ac50~60Hz
480V
NEMA, UL
600V
MCCB(Trip Units)
Amperes
F: Fixed
A: Adjustable
ATU
T: Thermal
M: Magnetic
FMU
FTU
MCP Amperes
MCP
MCS Amperes
MCS
Unit Mounted
Mechanical Lugs
Busbar connectors
Control Wire Terminal Kit
Terminal Shields
Interphase Barriers
Shunt Trip
Undervoltage Trip
Auxiliary Switch
Alarm Switch
Flange Cable Handle
Flange Variable-Depth Mechanism
Directly-Mounted Rotary Operating Handle
NEMA-Door-Mounted Operating Mechanisms
IEC-Door-Mounted Operating Mechanisms
Mechanical Interlocks
Handle Padlock Attachment
Dimensions
inches(mm)
2-Pole
3-Pole

11
N H L N H P
L
3
3
65
100
150
50
100
65
150
35
65
100
35
65
50
100
18
35
50
18
25
50
35
400~800A 800~1200A
●
●
800A 1200A
●
●
800A 1200A
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
W H D W H
D
8.5(216)
13(330)
6(152.5)
8.5(216)
16.26(413)
6(152.5)
UTS800
UTS1200
Maximum
Rated Current
(Amperes)
Circuit Breaker
Breaker Type
Number of Poles
Breaker Capacity
240V
(kA rms) ac50~60Hz
480V
NEMA, UL
600V
MCCB
Amperes
Trip Units
OCR: Electronics
OCR
MCP Amperes
MCP
MCS Amperes
MCS
Unit Mounted
Mechanical Lugs
Busbar connectors
Terminal Shields
Interphase Barriers
Shunt Trip
Undervoltage Trip
Auxiliary Switch
Alarm Switch
Flange Cable Handle
Flange Variable-Depth Mechanism
Directly-Mounted Rotary Operating Handle
NEMA-Door-Mounted Operating Mechanisms
IEC-Door-Mounted Operating Mechanisms
Mechanical Interlocks
Handle Padlock Attachment
Dimensions
Inches(mm)
3-Pole

UTE100-Frame
12
Dimensions
Product Description
�
UTE100 breaker is HACR rated
�
SWD switch duty rating
(applied only to 15 and 20A /347Vac or less)
�
HID high intensity discharge lighting rating
(15~50A /480Vac or less)
Trip Unit
�
FMU: Thermal(Adjustable), Instant(Fixed)
�
FTU: Thermal(Fixed), Instant(Fixed)
�
MCS: Only instant(Fixed)
Product Selection
Catalog Numbering (Product Selection)
(Depth: 3.44)
(Depth: 3.44)
2.01
5.12
2.99
5.12
Rating
FTU
UTE100
2P/3P
MAG TRIP
15
O
20
O
25
O
400A
30
O
40
O
50
O
60
O
800A
70
O
80
O
90
O
1000A
100
O
Rating
FMU
UTE100
3P
Rating
MAG
Range
TRIP
25
O
20~25A
400A
40
O
32~40A
60
O
48~60A
800A
80
O
64~80A
100
O
80~100A
1000A
Rating
MCS (2P/3P)
UTE100
MAG
(10
×
In)
100
1000A
NT
ATU
100A
3P
LL
UL
UTE100
Performance
Rating
80% 100%
kA
120/240Vac
E
ET
50
N
NT
65
240Vac
E
ET
50
N
NT
65
480Vac
E
ET
25
N
NT
35
600Y347Vac
E
ET
14
N
NT
18
Trip Unit
FTU: Fixed Thermal, Fixed Magnet
FMU: Adj. Thermal, Fixed Magnet
MCS: Molded Case Switch
Terminations
LL: Lugs Line/Load Side
LI: Lugs Line Side
LO: Lugs Load Side
-: Bolt-On
Poles
2: Two
3: Three
Suffix
UL: UL
Amperes
15
20
25
30
40
50
60
70
80
90
100
Brand & Frame: Susol 100AF

13
Table 2. Technical Data and Specifications
Rating Range
Spec
Circuit Breaker
UTE100
UTE100
Pole
2
3
Amperes
15~100A
15~100A
MCCB
FMU
-
■
FTU
■
■
MCS
Amperes
100A
100A
MCS
■
■
SIZE
W
2.01(51)
2.99(76)
Inch
H
5.12(130)
5.12(130)
(mm)
D
3.44(87.5)
3.44(87.5)
Interrupting Rating
E
50
50
kA rms (240VAC)
N
65
65
Interrupting Rating
E
25
25
kA rms (480VAC)
N
35
35
Interrupting Rating
E
14
14
kA rms (600Y347VAC)
N
18
18
Table 3. Tightening Torque for Lugs
Terminal
Breaker
AWG
Torque
Lug Type
Body
Wire Type
Amps
Wire
N.m(lb-in)
Material
Range
Range
15~30A
14~10
4(35.4)
60
℃
40A
8
5(44.3)
50~80A
6~3
6(53.1)
CU
90~100A
2~1
7(61.9)
15~30A
14~10
4(35.4)
AL100TE
Aluminum
75
℃
40~50A
8
5(44.3)
60~100A
6~3
6(53.1)
60
℃
40~60A
6~3
6(53.1)
AL
70~80A
2~1
7(61.9)
75
℃
50~70A
6~3
6(53.1)
80~100A
2~1/0
7(61.9)
Table 4. Enclosure Dimensions
*Applicable in indicated pole position-not synchronous.
Circuit Breaker
Amperage
Enclosure Dimension(W
×
H
×
D)(mm)
80%
100%
UTE100
15~100A
210
×
439.4
×
101.6
Table 5. Inner Accessory
Type
Right(T)
AX
1
AL
1
AX+AL
1
SHT
1
UVT
1
Type
Left(R)
Right(T)
AX
1
1
AL
1
1
AX+AL
1
1
SHT
1
UVT
1

UTE100-Frame
14
Table 5. Undervoltage Trip UVT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.1
23
Voltage
AC/DC 100~110V
0.73
0.75
5.8
AC/DC 200~220V
1.21
1.35
5.4
AC 380~440V
1.67
-
3.8
AC 440~480V
1.68
-
3.5
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating
Trip
20~70% Vn
voltage range
Reset/Closing
≥
0.85Vn
Table 6. Shunt Trip SHT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
AC/DC 12V
0.35
0.36
30
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.1
23
Voltage
AC/DC 60V
1.2
1.22
20
AC/DC 100~130V
0.73
0.75
5.8
AC/DC 200~250V
1.21
1.35
5.4
AC 380~450V
1.67
-
3.8
AC 440~500V
1.68
-
3.5
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating voltage range
AC: 0.7~1.1Vn, DC: 0.8~1.1Vn
Table 7. Handle [Rotary and Cable]
Type
Directly-Mounted
Door-Mounted
Flange Handle with
Flange Handle with
Cable Operation Mechanism
Variable Depth Mechanism
IEC
-
-
Standard
NEMA Type 1
NEMA
-
Standard
NEMA Type 1, 12, 3, 3R, 4, 4X

UTS150-Frame
15
Dimensions
Trip Unit
�
FMU: Thermal (Adjustable), Instant(Fixed)
�
FTU: Thermal(Fixed), Instant(Fixed)
�
ATU: Thermal(Adjustable), Instant(Adjustable)
�
MCP: Only Instant(Adjustable)
�
MCS: Only instant(Fixed)
Product Description
�
UTS150 breaker is HACR rated
(Depth: 3.44)
4.13
6.46
Rating
FTU
UTS150
2P/3P
MAG TRIP
40
O
500A
50
O
60
O
70
O
800A
80
O
90
O
1000A
100
O
125
O
1500A
150
O
FMU
Rating
Rating
UTS150
2P/3P
Range
MAG TRIP
(0.8~1
×
In)
40
O
32~40A
500A
60
O
48~60A
800A
80
O
64~80A
800A
100
O
80~100A
1000A
150
O
120~150A
1500A
ATU
Rating
Rating
MAG TRIP
UTS150
2P/3P
Range
(5~10
×
In)
(0.8~1
×
In)
100
O
80~100A
500~1000A
150
O
120~150A 750~1500A
Rating
MCS (2P/3P)
UTS150
MAG TRIP
(10
×
In)
150
1500A
Rating
MCP (3P)
UTS150
MAG TRIP
(6~12
×
In)
1.6
10~20A
3.2
20~40A
6.3
40~80A
12
70~140A
20
120~240A
32
190~380A
50
300~600A
60
360~720A
100
600~1200A
150
900~1800A
Product Selection
Catalog Numbering (Product Selection)
NT
ATU
150A
3P
LL
UL
UTS150
Performance
Rating
80% 100%
kA
N
NT
65
240VAC
H
HT
100
L
LT
150
N
NT
35
480VAC
H
HT
65
L
LT
100
N
NT
18
600VAC
H
HT
35
L
LT
50
Trip Unit
FTU: Fixed Thermal, Fixed Magnet
FMU: Adj. Thermal, Fixed Magnet
ATU: Adj. Thermal & Magnet
MCP: Motor Circuit Protector
MCS: Molded Case Switch
Terminations
LL: Lugs Line/Load Side
LI: Lugs Line Side
LO: Lugs Load Side
-: Bolt-On
Poles
2: Two
3: Three
Suffix
UL: UL
Brand & Frame: Susol 150AF
Amperes
MCCB
MCP
40
1.6
50
3.2
60
6.3
70
12
80
20
90
32
100
50
125
60
150
100
150

UTS150-Frame
16
Table 2. Technical Data and Specifications
Rating Range
Spec
Circuit Breaker
UTS150
Pole
2/3
Amperes
40~150A
MCCB
ATU
■
FMU
■
FTU
■
Amperes
1.6~60A
MCP 70~150A
MCP
■
MCS
Amperes
150A
MCS
■
SIZE
W 4.13(105)
Inch
H 6.46(165)
(mm) D
3.44(87.5)
Interrupting Rating
N
65
kA rms
H
100
(240VAC) L
150
Interrupting Rating
N
35
kA rms
H
65
(480VAC) L
100
Interrupting Rating
N
18
kA rms
H
35
(600VAC) L
50
Table 3. Tightening Torque for Lugs
Terminal
Breaker
AWG
Torque
Lug Type
Body
Amps
Wire Type
Wire
N.m(lb-in)
Material Range
Range
~15A
Cu/Al
14
4.5(39.8)
20~30A
Cu/Al
12~10
6(53.1)
AL150TS
Aluminum
40~175A
Cu/Al
8-2/0
15.1(133.6)
50~70A
Al
6~3
6(53.1)
90~150A
Al
2~3/0
15.6(160.0)
Table 4. Enclosure Dimensions
Circuit Breaker
Amperage
Enclosure Dimension(W
×
H
×
D)(mm)
80%
100%
UTS150
40~150A
218
×
460
×
102
Table 5. Inner Accessory
Type
Left(R)
Right(T)
AX
1
1
AL
1
-
SHT
1*
-
UVT
1*
-
*Applicable in indicated pole position-not synchronous.

17
Table 5. Undervoltage Trip UVT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.1
23
Voltage
AC/DC 110~130V
0.73
0.75
5.8
AC/DC 220~240V / DC 250V
1.21
1.35
5.4
AC 380~440V
1.67
-
3.8
AC 440~480V
1.68
-
3.5
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating
Trip
35~70% Vn
voltage range
Reset/Closing
≥
0.85Vn
Table 6. Shunt Trip SHT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
DC 12V
-
0.36
30
AC/DC 24V
0.58
0.58
24
Voltage
AC/DC 48V
1.22
1.23
25
AC/DC 110~130V
1.36
1.37
10.5
AC 220~240V/DC250V
1.8
1.88
7.5
AC 380~500V
1.15
-
2.3
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating voltage range
0.7~1.1Vn
Table 7. Handle [Rotary and Cable]
Type
Directly-Mounted
Door-Mounted
Flange Handle with
Flange Handle with
Cable Operation Mechanism
Variable Depth Mechanism
IEC
-
-
Standard
NEMA Type 1
NEMA
-
Standard
NEMA Type 1, 12, 3, 3R, 4, 4X

UTS250-Frame
18
Product Description
�
UTS250 breaker is HACR rated
Trip Unit
�
FMU: Thermal (Adjustable), Instant(Fixed)
�
FTU: Thermal(Fixed), Instant(Fixed)
�
ATU: Thermal(Adjustable), Instant(Adjustable)
�
MCP: Only Instant(Adjustable)
�
MCS: Only instant(Fixed)
Dimensions
(Depth: 3.44)
4.13
7.48
Rating
FTU
UTS250
2P/3P
MAG TRIP
150
O
1500A
175
O
1750A
200
O
2000A
225
O
2250A
250
O
2500A
FMU
Rating
Rating
UTS250
2P/3P
Range
MAG TRIP
(0.8~1
×
In)
160
O
128~160A
1600A
200
O
160~200A
2000A
250
O
200~250A
2500A
ATU
Rating
Rating
MAG TRIP
UTS250
2P/3P
Range
(5~10
×
In)
(0.8~1
×
In)
160
O
128~160A
800~1600A
200
O
160~200A 1000~2000A
250
O
200~250A 1250~2500A
Rating
MCS (2P/3P)
UTS250
MAG TRIP
(10
×
In)
175
1750A
250
2500A
Rating
MCP (3P)
UTS250
MAG TRIP
(6~12
×
In)
220
1320~2640A
Product Selection
Catalog Numbering (Product Selection)
NT
ATU
250A
3P
LL
UL
UTS250
Performance
Rating
80% 100%
kA
N
NT
65
240VAC
H
HT
100
L
LT
150
N
NT
35
480VAC
H
HT
65
L
LT
100
N
NT
18
600VAC
H
HT
35
L
LT
50
Trip Unit
FTU: Fixed Thermal, Fixed Magnet
FMU: Adj. Thermal, Fixed Magnet
ATU: Adj. Thermal & Magnet
MCP: Motor Circuit Protector
MCS: Molded Case Switch
Terminations
LL: Lugs Line/Load Side
LI: Lugs Line Side
LO: Lugs Load Side
-: Bolt-On
Poles
2: Two
3: Three
Suffix
UL: UL
Brand & Frame: Susol 250AF
Amperes
150
160
175
200
225
250

19
Table 2. Technical Data and Specifications
Rating Range
Spec
Circuit Breaker
UTS250
Pole
2/3
Amperes
150~250A
MCCB
ATU
■
FMU
■
FTU
■
MCP
Amperes
220A
MCP
■
MCS
Amperes
175, 250A
MCS
■
SIZE
W 4.13(105)
Inch
H 7.48(190)
(mm) D
3.44(87.5)
Interrupting Rating
N
65
kA rms
H
100
(240VAC) L
150
Interrupting Rating
N
35
kA rms
H
65
(480VAC) L
100
Interrupting Rating
N
18
kA rms
H
35
(600VAC) L
50
Table 3. Tightening Torque for Lugs
Terminal
Breaker
AWG
Torque
Lug Type
Body
Amps
Wire Type
Wire
N.m(lb-in)
Material Range
Range
AL250TS
Aluminum
150A
Cu/Al
1/0-4/0
28.8(254.9)
250A
Cu/Al
250~350
39.6(350.5)
Table 4. Enclosure Dimensions
Circuit Breaker
Amperage
Enclosure Dimension(W
×
H
×
D)(mm)
80%
100%
UTS250
150~250A
308
×
724
×
136
Table 5. Inner Accessory
Type
Left(R)
Right(T)
AX
1
1
AL
1
-
SHT
1*
-
UVT
1*
-
*Applicable in indicated pole position-not synchronous.

UTS250-Frame
20
Table 7. Handle [Rotary and Cable]
Type
Directly-Mounted
Door-Mounted
Flange Handle with
Flange Handle with
Cable Operation Mechanism
Variable Depth Mechanism
IEC
-
-
Standard
NEMA Type 1
NEMA
-
Standard
NEMA Type 1, 12, 3, 3R, 4, 4X
Table 5. Undervoltage Trip UVT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.1
23
Voltage
AC/DC 110~130V
0.73
0.75
5.8
AC 220~240V / DC 250V
1.21
1.35
5.4
AC 380~440V
1.67
-
3.8
AC 440~480V
1.68
-
3.5
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating
Trip
35~70% Vn
voltage range
Reset/Closing
≥
0.85Vn
Table 6. Shunt Trip SHT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
DC 12V
-
0.36
30
AC/DC 24V
0.58
0.58
24
Voltage
AC/DC 48V
1.22
1.23
25
AC/DC 110~130V
1.36
1.37
10.5
AC 220~240V/DC250V
1.8
1.88
7.5
AC 380~500V
1.15
-
2.3
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating voltage range
0.7~1.1Vn

UTS400-Frame
21
Trip Unit
�
FMU: Thermal (Adjustable), Instant(Fixed)
�
FTU: Thermal(Fixed), Instant(Fixed)
�
ATU: Thermal(Adjustable), Instant(Adjustable)
�
MCP: Only Instant(Adjustable)
�
MCS: Only instant(Fixed)
Product Description
�
UTS400 breaker is HACR rated
Dimensions
(Depth: 4.33)
5.51
11.42
Rating
FTU
UTS400
2P/3P
MAG TRIP
250
O
2500A
300
O
3000A
350
O
3500A
400
O
4000A
FMU
Rating
Rating
UTS400
2P/3P
Range
MAG TRIP
(0.8~1
×
In)
300
O
240~300A
3000A
400
O
320~400A
4000A
ATU
Rating
Rating
MAG TRIP
UTS400
2P/3P
Range
(5~10
×
In)
(0.8~1
×
In)
300
O
240~300A 1500~3000A
400
O
320~400A 2000~4000A
Rating
MCS (2P/3P)
UTS400
MAG TRIP
(10
×
In)
400
4000A
Rating
MCP (3P)
UTS400
MAG TRIP
(6~12
×
In)
320
1920~3840A
Product Selection
Catalog Numbering (Product Selection)
NT
ATU
400A
3P
LL
UL
UTS400
Performance
Rating
80% 100%
kA
N
NT
65
240VAC
H
HT
100
L
LT
150
N
NT
35
480VAC
H
HT
65
L
LT
100
N
NT
18
600VAC
H
HT
35
L
LT
50
Trip Unit
FTU: Fixed Thermal, Fixed Magnet
FMU: Adj. Thermal, Fixed Magnet
ATU: Adj. Thermal & Magnet
MCP: Motor Circuit Protector
MCS: Molded Case Switch
Terminations
LL: Lugs Line/Load Side
LI: Lugs Line Side
LO: Lugs Load Side
-: Bolt-On
Poles
2: Two
3: Three
Suffix
UL: UL
Brand & Frame: Susol 400AF
Amperes
250
300
350
400

UTS400-Frame
22
Table 2. Technical Data and Specifications
Rating Range
Spec
Circuit Breaker
UTS400
Pole
2/3
Amperes
250~400A
MCCB
ATU
■
FMU
■
FTU
■
MCP
Amperes
320A
MCP
■
MCS
Amperes
400A
MCS
■
SIZE
W 5.51(140)
Inch
H 11.42(290)
(mm) D
4.33(110)
Interrupting Rating
N
65
kA rms
H
100
(240VAC) L
150
Interrupting Rating
N
35
kA rms
H
65
(480VAC) L
100
Interrupting Rating
N
18
kA rms
H
35
(600VAC) L
50
Table 3. Tightening Torque for Lugs
Terminal
Breaker
AWG
Torque
Lug Type
Body
Amps
Wire Type
Wire
N.m(lb-in)
Material Range
Range
AL400TS
Aluminum
300A
Cu/Al
1/0~300
40.5(358.5)
400A
Cu/Al
350~600
54(477.9)
Table 4. Enclosure Dimensions
Circuit Breaker
Amperage
Enclosure Dimension(W
×
H
×
D)(mm)
80%
100%
UTS400
250~400A
350
×
1020
×
152
350
×
1020
×
182
Table 5. Inner Accessory
Type
Left(R)
Right(T)
AX
3
-
AL
-
1
SHT
1*
-
UVT
1*
-
*Applicable in indicated pole position-not synchronous.

23
Table 7. Handle [Rotary and Cable]
Type
Directly-Mounted
Door-Mounted
Flange Handle with
Flange Handle with
Cable Operation Mechanism
Variable Depth Mechanism
IEC
-
-
Standard
NEMA Type 1
NEMA
-
Standard
NEMA Type 1, 12, 3, 3R, 4, 4X
Table 5. Undervoltage Trip UVT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.1
23
Voltage
AC/DC 110~130V
0.73
0.75
5.8
AC 220~240V / DC 250V
1.21
1.35
5.4
AC 380~440V
1.67
-
3.8
AC 440~480V
1.68
-
3.5
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating
Trip
35~70% Vn
voltage range
Reset/Closing
≥
0.85Vn
Table 6. Shunt Trip SHT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
DC 12V
-
0.36
30
AC/DC 24V
0.58
0.58
24
Voltage
AC/DC 48V
1.22
1.23
25
AC/DC 110~130V
1.36
1.37
10.5
AC 220~240V/DC250V
1.8
1.88
7.5
AC 380~500V
1.15
-
2.3
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating voltage range
0.7~1.1Vn

UTS600-Frame
24
Trip Unit
�
FMU: Thermal (Adjustable), Instant(Fixed)
�
FTU: Thermal(Fixed), Instant(Fixed)
�
ATU: Thermal(Adjustable), Instant(Adjustable)
�
MCP: Only Instant(Adjustable)
�
MCS: Only instant(Fixed)
Product Description
�
UTS600 breaker is HACR rated
Dimensions
(Depth: 4.33)
5.51
13.39
Rating
FTU
UTS600
2P/3P
MAG TRIP
500
O
5000A
600
O
6000A
FMU
Rating
Rating
UTS600
2P/3P
Range
MAG TRIP
(0.8~1
×
In)
500
O
400~500A 2500~5000A
600
O
480~600A 3000~6000A
ATU
Rating
Rating
MAG TRIP
UTS600
2P/3P
Range
(5~10
×
In)
(0.8~1
×
In)
500
O
400~500A 2500~5000A
600
O
480~600A 3000~6000A
Rating
MCS (2P/3P)
UTS600
MAG TRIP
(10
×
In)
600
6000A
Rating
MCP (3P)
UTS600
MAG TRIP
(6~12
×
In)
500
3000~6000A
Product Selection
Catalog Numbering (Product Selection)
NT
ATU
600A
3P
LL
UL
UTS600
Performance
Rating
80% 100%
kA
N
NT
65
240VAC
H
HT
100
L
LT
150
N
NT
35
480VAC
H
HT
65
L
LT
100
N
NT
18
600VAC
H
HT
35
L
LT
50
Trip Unit
FTU: Fixed Thermal, Fixed Magnet
FMU: Adj. Thermal, Fixed Magnet
ATU: Adj. Thermal & Magnet
MCP: Motor Circuit Protector
MCS: Molded Case Switch
Terminations
LL: Lugs Line/Load Side
LI: Lugs Line Side
LO: Lugs Load Side
-: Bolt-On
Poles
2: Two
3: Three
Suffix
UL: UL
Brand & Frame: Susol 600AF
Amperes
500
600

25
Table 2. Technical Data and Specifications
Rating Range
Spec
Circuit Breaker
UTS600
Pole
2/3
Amperes
500~600A
MCCB
ATU
■
FMU
■
FTU
■
MCP
Amperes
500A
MCP
■
MCS
Amperes
600A
MCS
■
SIZE
W 5.51(140)
Inch
H 13.39(340)
(mm) D
4.33(110)
Interrupting Rating
N
65
kA rms
H
100
(240VAC) L
150
Interrupting Rating
N
35
kA rms
H
65
(480VAC) L
100
Interrupting Rating
N
18
kA rms
H
35
(600VAC) L
50
Table 3. Tightening Torque for Lugs
Terminal
Breaker
AWG
Torque
Lug Type
Body
Amps
Wire Type
Wire
N.m(lb-in)
Material Range
Range
AL600TS
Aluminum
500A
Cu/Al
2/0~350
40.5(358.5)
600A
Cu/Al
400~500
40.5(358.5)
Table 4. Enclosure Dimensions
Circuit Breaker
Amperage
Enclosure Dimension(W
×
H
×
D)(mm)
80%
100%
UTS600
500~600A
350
×
1020
×
152
360
×
1050
×
182
Table 5. Inner Accessory
Type
Left(R)
Right(T)
AX
3
-
AL
-
1
SHT
1*
-
UVT
1*
-
*Applicable in indicated pole position-not synchronous.

UTS600-Frame
26
Table 7. Handle [Rotary and Cable]
Type
Directly-Mounted
Door-Mounted
Flange Handle with
Flange Handle with
Cable Operation Mechanism
Variable Depth Mechanism
IEC
-
-
Standard
NEMA Type 1
NEMA
-
Standard
NEMA Type 1, 12, 3, 3R, 4, 4X
Table 5. Undervoltage Trip UVT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.1
23
Voltage
AC/DC 110~130V
0.73
0.75
5.8
AC 220~240V / DC 250V
1.21
1.35
5.4
AC 380~440V
1.67
-
3.8
AC 440~480V
1.68
-
3.5
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating
Trip
35~70% Vn
voltage range
Reset/Closing
≥
0.85Vn
Table 6. Shunt Trip SHT
Control voltage,Ue
Power consumption
AC (VA)
DC (W)
mA
DC 12V
-
0.36
30
AC/DC 24V
0.58
0.58
24
Voltage
AC/DC 48V
1.22
1.23
25
AC/DC 110~130V
1.36
1.37
10.5
AC 220~240V/DC250V
1.8
1.88
7.5
AC 380~500V
1.15
-
2.3
Max.opening time
50ms (max.)
Tightening torque of terminal screw
8.2 kgf
�
cm
Operating voltage range
0.7~1.1Vn

UTS800-Frame
27
Product Description
�
UTS800 breaker is HACR rated
Trip Unit
a) UV: Under Voltage // OV: Over Voltage // OF: Over Frequency // UF: Under Frequency // RV: Reverse power // Vun: Voltage Unbalance // Cun: Current Unbalance
b) V: Voltage // A: Ampere // W: Watt // P: Power // F: Frequency // PF: Power factor
Dimensions
(Depth: 4.33)
8.5
13
Long time delay / Short time delay
The range of rated current setting is same with 4Types
N type
Instantaneous / Ground faults / Self power
but P/S type is able to set detail adjustment of rated current
※
LCD/SMPS is Removed from A type
per 1A (Fine Adjustable)
All function of N type / Earth Leakage (Except residual current)
■
Ir (rated current): 0.4~1.0 In
A type
ZSI / COMM. (MODBUS, Profibus)
■
Tr (long time tripping delay): 0.5~20 Sec
AC110~220V / DC24~48V
■
Isd (short time current): 1.5~10 Ir
Fault Recording 10ea
■
Tsd (short time tripping delay): 0.05~0.4 Sec
All function of A type (UV/OV/OF/UF/RV/Vun/Cun)
a)
■
Ii (instantaneous current): 2~15 In
P type
Measuring (V/A/W/P/F/PF)
b)
■
Tg (ground fault tripping delay): 0.05~0.4 Sec
Fault Recording 256ea / Event Recording 256ea
■
Ig (ground fault current): 0.2~1In
S type
All function of P type. Display Harmonics and wave forms
MCP800
Instant Only
Ii (adjustable instant): 2~12In
MCS
Instant Only
Ii (fixed instant current): 12,000A
NT
N
G
O
800A
3P
LL
UL
UTS800
OCR-1
N: Normal
A: Ammeter
P: Power meter
S: Super meter
MCP: Motor Circuit Protector
MCS: Molded Case Switch
OCR-II
G: Communication(X)
E: Com.(O)+Outer CT(G/F)
C: Communication(O)
X: Com.(O)+Outer CT(G/F)
OCR-III
0: Power(x), 60Hz
1: AC/DC 110~220V, 60Hz
2: AC/DC 24~48V, 60Hz
5: Power(x), 50Hz
6: AC/DC 110~220V, 50Hz
7: AC/DC 24~48V, 50Hz
Terminations
LL: Lugs Line/Load Side
LI: Lugs Line Side
LO: Lugs Load Side
-: Bolt-On
Poles
3: Three
Suffix
UL: UL
Amperes
400
600
630
800
Product Selection
Catalog Numbering (Product Selection)
Performance
Rating
80% 100%
kA
N
NT
65
240VAC
H
HT
100
L
LT
150
N
NT
35
480VAC
H
HT
65
L
LT
100
N
NT
18
600VAC
H
HT
35
L
LT
50
Brand & Frame: Susol 800AF

UTS800-Frame
28
Table 2. Technical Data and Specifications
Rating Range
Spec
Circuit Breaker
UTS800
Pole
3
MCCB
Amperes
400~800A
OCR
N/A/P/S
MCP
Amperes
800A
MCP
MCP800
MCS
Amperes
800A
MCS
MCS
SIZE
W
8.5(216)
Inch
H
13(330)
(mm)
D
6(152.5)
Interrupting Rating
N
50
kA rms
H
100
(240VAC)
L
150
Interrupting Rating
N
35
kA rms
H
65
(480VAC)
L
100
Interrupting Rating
N
18
kA rms
H
35
(600VAC)
L
50
Table 3. Tightening Torque for Lugs
Terminal
Breaker
AWG
Torque
Lug Type
Body
Amps
Wire Type
Wire
N.m(lb-in)
Material Range
Range
AL800TS
Aluminum
400~800A
Cu/Al
3/0~300
45(398.3)
(400 AL)
Table 4. Enclosure Dimensions
Circuit Breaker
Amperage
Enclosure Dimension(W
×
H
×
D)(mm)
80%
100%
UTS800
400~800A
514.4
×
1318.3
×
196.9
Table 5. Inner Accessory
Type
Right(T)
AX
3
AL
1
SHT
1
UVT
1
*Applicable in indicated pole position-not synchronous.

29
Table 5. Undervoltage Trip UVT
Control voltage,Ue
Power consumption(VA or W)
Max.opening
Inrush
Steady-state
time(ms)
DC 24~30V
AC 48 / DC 48~60V
Voltage
AC/DC 100~130V
200
5
50 (max.)
AC/DC 200~250V
AC 380~480V
Operating
Drop Out
0.44~0.66Vn
voltage range
Pick up
0.65~0.85Vn
Table 6. Shunt Trip SHT
Control voltage,Ue
Operating
Power consumption(VA or W)
voltage range
Inrush
Steady-state
DC 24~30V
0.6~1.1Vn
AC 48 / DC 48~60V
0.6~1.1Vn
Voltage
AC/DC 100~130V
0.56~1.1Vn
200
5
AC/DC 200~250V
0.56~1.1Vn
AC 380~480V
0.56~1.1Vn
Max.opening time
40ms (max.)
Table 7. Handle [Rotary and Cable]
Type
Directly-Mounted
Door-Mounted
Flange Handle with
Flange Handle with
Cable Operation Mechanism
Variable Depth Mechanism
IEC
-
-
Standard
NEMA Type 1
NEMA
-
Standard
NEMA Type 1, 12, 3, 3R, 4, 4X

UTS1200-Frame
30
Product Description
�
UTS1200 breaker is HACR rated
Trip Unit
a) UV: Under Voltage // OV: Over Voltage // OF: Over Frequency // UF: Under Frequency // RV: Reverse power // Vun: Voltage Unbalance // Cun: Current Unbalance
b) V: Voltage // A: Ampere // W: Watt // P: Power // F: Frequency // PF: Power factor
Dimensions
(Depth: 6)
16.26
Long time delay / Short time delay
The range of rated current setting is same with 4Types
N type
Instantaneous / Ground faults / Self power
but P/S type is able to set detail adjustment of rated current
※
LCD/SMPS is Removed from A type
per 1A (Fine Adjustable)
All function of N type / Earth Leakage (Except residual current)
■
Ir (rated current): 0.4~1.0 In
A type
ZSI / COMM. (MODBUS, Profibus)
■
Tr (long time tripping delay): 0.5~20 Sec
AC110~220V / DC24~48V
■
Isd (short time current): 1.5~10 Ir
Fault Recording 10ea
■
Tsd (short time tripping delay): 0.05~0.4 Sec
All function of A type (UV/OV/OF/UF/RV/Vun/Cun)
a)
■
Ii (instantaneous current): 2~15 In
P type
Measuring (V/A/W/P/F/PF)
b)
■
Tg (ground fault tripping delay): 0.05~0.4 Sec
Fault Recording 256ea / Event Recording 256ea
■
Ig (ground fault current): 0.2~1In
S type
All function of P type. Display Harmonics and wave forms
MCP1200
Instant Only
Ii (adjustable instant): 2~8In
MCS
Instant Only
Ii (fixed instant current): 18,000A
8.5
NT
N
G
O
1200A
3P
LL
UL
UTS1200
OCR-1
N: Normal
A: Ammeter
P: Power meter
S: Super meter
MCP: Motor Circuit Protector
MCS: Molded Case Switch
OCR-II
G: Communication(X)
E: Com.(O)+Outer CT(G/F)
C: Communication(O)
X: Com.(O)+Outer CT(G/F)
OCR-III
0: Power(x), 60Hz
1: AC/DC 110~220V, 60Hz
2: AC/DC 24~48V, 60Hz
5: Power(x), 50Hz
6: AC/DC 110~220V, 50Hz
7: AC/DC 24~48V, 50Hz
Terminations
LL: Lugs Line/Load Side
LI: Lugs Line Side
LO: Lugs Load Side
-: Bolt-On
Poles
3: Three
Suffix
UL: UL
Amperes
400
600
630
800
Product Selection
Catalog Numbering (Product Selection)
Performance
Rating
80% 100%
kA
N
NT
65
240VAC
H
HT
100
L
LT
150
N
NT
35
480VAC
H
HT
65
L
LT
100
N
NT
18
600VAC
H
HT
35
L
LT
50
Brand & Frame: Susol 1200AF

31
Table 2. Technical Data and Specifications
Rating Range
Spec
Circuit Breaker
UTS1200
Pole
3
MCCB
Amperes
800~1200A
OCR
N/A/P/S
MCP
Amperes
1200A
MCP
MCP1200
MCS
Amperes
1200A
MCS
MCS
SIZE
W
8.5(216)
Inch
H
16.26(413)
(mm)
D
6(152.5)
Interrupting Rating
N
50
kA rms
H
100
(240VAC)
P
65
L
150
Interrupting Rating
N
35
kA rms
H
65
(480VAC)
P
50
L
100
Interrupting Rating
N
18
kA rms
H
25
(600VAC)
P
50
L
35
Table 3. Tightening Torque for Lugs
Terminal
Breaker
AWG
Torque
Lug Type
Body
Amps
Wire Type
Wire
N.m(lb-in)
Material Range
Range
AL1200TS
Aluminum
800~1200A
Cu/Al
3/0~350
45(398.3)
(500 AL)
Table 4. Enclosure Dimensions
Circuit Breaker
Amperage
Enclosure Dimension(W
×
H
×
D)(mm)
80%
100%
UTS1200
800~1200A
514.4
×
1318.3
×
196.9
584.2
×
1581.2
×
374.7
Table 5. Inner Accessory
Type
Right(T)
AX
3
AL
1
SHT
1
UVT
1
*Applicable in indicated pole position-not synchronous.

UTS1200-Frame
32
Table 7. Handle [Rotary and Cable]
Type
Directly-Mounted
Door-Mounted
Flange Handle with
Flange Handle with
Cable Operation Mechanism
Variable Depth Mechanism
IEC
-
-
Standard
NEMA Type 1
NEMA
-
Standard
NEMA Type 1, 12, 3, 3R, 4, 4X
Table 5. Undervoltage Trip UVT
Control voltage,Ue
Power consumption(VA or W)
Max.opening
Inrush
Steady-state
time(ms)
DC 24~30V
AC 48 / DC 48~60V
Voltage
AC/DC 100~130V
200
5
50 (max.)
AC/DC 200~250V
AC 380~480V
Operating
Drop Out
0.44~0.66Vn
voltage range
Pick up
0.65~0.85Vn
Table 6. Shunt Trip SHT
Control voltage,Ue
Operating
Power consumption(VA or W)
voltage range
Inrush
Steady-state
DC 24~30V
0.6~1.1Vn
AC 48 / DC 48~60V
0.6~1.1Vn
Voltage
AC/DC 100~130V
0.56~1.1Vn
200
5
AC/DC 200~250V
0.56~1.1Vn
AC 380~480V
0.56~1.1Vn
Max.opening time
40ms (max.)

Memo